2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital
BACKGROUND: The severity of coronavirus disease-2019 (COVID-19) has decreased owing to antiviral agents and herd immunity; however, transmission among hospitalised patients could be fatal. Therefore, strategies to prevent the spread of COVID-19 in medical institutions are crucial. This study aimed t...
Autores principales: | , , , , , , , , , |
---|---|
Formato: | Online Artículo Texto |
Lenguaje: | English |
Publicado: |
Oxford University Press
2023
|
Materias: | |
Acceso en línea: | https://www.ncbi.nlm.nih.gov/pmc/articles/PMC10678898/ http://dx.doi.org/10.1093/ofid/ofad500.1952 |
_version_ | 1785150466362966016 |
---|---|
author | Park, Se Yoon Yu, Jungyeon Song, Jin Su Lee, Shin Young Kim, Jin Hwa Jeong, Yeon Su Oh, Sun Mi Kim, Tae Hyong Bae, Sanghwan Lee, Eunjung |
author_facet | Park, Se Yoon Yu, Jungyeon Song, Jin Su Lee, Shin Young Kim, Jin Hwa Jeong, Yeon Su Oh, Sun Mi Kim, Tae Hyong Bae, Sanghwan Lee, Eunjung |
author_sort | Park, Se Yoon |
collection | PubMed |
description | BACKGROUND: The severity of coronavirus disease-2019 (COVID-19) has decreased owing to antiviral agents and herd immunity; however, transmission among hospitalised patients could be fatal. Therefore, strategies to prevent the spread of COVID-19 in medical institutions are crucial. This study aimed to investigate ventilation strategies to prevent nosocomial transmission of COVID-19. METHODS: We retrospectively conducted an epidemiological investigation of the severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) outbreak between 12 February and 5 March 2021 in a referral teaching hospital in Korea. The pressure difference and air change per hour (ACH) of the rooms were measured in the largest outbreak ward. Airflow dynamics were measured based on the opening or closing of the outside window and door by using an oil droplet generator, indoor air quality sensor, and particle image velocimetry in the index patient’s room, corridor, and opposite rooms. RESULTS: During the outbreak, 283 COVID-19 cases were identified. The largest outbreak occurred at the 8(th) floor followed by the 9(th) and 7(th) floors of the main building. According to an epidemiological investigation, the SARS-CoV-2 spread occurred sequentially from the index room to the nearest room, especially the opposite. The aerodynamic study demonstrated that droplet-like particles in the index room diffused through the corridor and the opposite room through the opening door (Figure 1). The mean ACH of the rooms on the 8(th) floor was 1.44; the air supply volume was 15.9% larger than the exhaust volume, forming a positive pressure. Compared with the open-door condition, droplet-like particles did not diffuse into an adjacent room facing each other in the closed-door condition. The concentration of droplet-like particles in the ward was lowered during natural ventilation, and their spread to an adjacent room facing the corridor was also reduced (Figure 2). Location of the index patient and detection sensor of the droplet-like particles [Figure: see text] Relative ratio in measurement of droplet-like particles, PM2.5, concentration according to natural ventilation conditions [Figure: see text] (A) Window closed/indoor-open (usual condition: ventilation with the heating, ventilation, and air conditioning [HVAC] system without natural ventilation), (B) Window open/indoors closed (condition for improvement: close the door and perform natural ventilation for each room), (C) Window and indoor opening (condition for improvement: opening all doors and windows in all the rooms and maximising natural ventilation). CONCLUSION: The spread of droplet-like particles between rooms could be attributed to the pressure difference between the rooms and corridor. To prevent the spread of transmission between rooms, increasing the ACH in the room by maximising natural and mechanical ventilation is essential. DISCLOSURES: All Authors: No reported disclosures |
format | Online Article Text |
id | pubmed-10678898 |
institution | National Center for Biotechnology Information |
language | English |
publishDate | 2023 |
publisher | Oxford University Press |
record_format | MEDLINE/PubMed |
spelling | pubmed-106788982023-11-27 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital Park, Se Yoon Yu, Jungyeon Song, Jin Su Lee, Shin Young Kim, Jin Hwa Jeong, Yeon Su Oh, Sun Mi Kim, Tae Hyong Bae, Sanghwan Lee, Eunjung Open Forum Infect Dis Abstract BACKGROUND: The severity of coronavirus disease-2019 (COVID-19) has decreased owing to antiviral agents and herd immunity; however, transmission among hospitalised patients could be fatal. Therefore, strategies to prevent the spread of COVID-19 in medical institutions are crucial. This study aimed to investigate ventilation strategies to prevent nosocomial transmission of COVID-19. METHODS: We retrospectively conducted an epidemiological investigation of the severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) outbreak between 12 February and 5 March 2021 in a referral teaching hospital in Korea. The pressure difference and air change per hour (ACH) of the rooms were measured in the largest outbreak ward. Airflow dynamics were measured based on the opening or closing of the outside window and door by using an oil droplet generator, indoor air quality sensor, and particle image velocimetry in the index patient’s room, corridor, and opposite rooms. RESULTS: During the outbreak, 283 COVID-19 cases were identified. The largest outbreak occurred at the 8(th) floor followed by the 9(th) and 7(th) floors of the main building. According to an epidemiological investigation, the SARS-CoV-2 spread occurred sequentially from the index room to the nearest room, especially the opposite. The aerodynamic study demonstrated that droplet-like particles in the index room diffused through the corridor and the opposite room through the opening door (Figure 1). The mean ACH of the rooms on the 8(th) floor was 1.44; the air supply volume was 15.9% larger than the exhaust volume, forming a positive pressure. Compared with the open-door condition, droplet-like particles did not diffuse into an adjacent room facing each other in the closed-door condition. The concentration of droplet-like particles in the ward was lowered during natural ventilation, and their spread to an adjacent room facing the corridor was also reduced (Figure 2). Location of the index patient and detection sensor of the droplet-like particles [Figure: see text] Relative ratio in measurement of droplet-like particles, PM2.5, concentration according to natural ventilation conditions [Figure: see text] (A) Window closed/indoor-open (usual condition: ventilation with the heating, ventilation, and air conditioning [HVAC] system without natural ventilation), (B) Window open/indoors closed (condition for improvement: close the door and perform natural ventilation for each room), (C) Window and indoor opening (condition for improvement: opening all doors and windows in all the rooms and maximising natural ventilation). CONCLUSION: The spread of droplet-like particles between rooms could be attributed to the pressure difference between the rooms and corridor. To prevent the spread of transmission between rooms, increasing the ACH in the room by maximising natural and mechanical ventilation is essential. DISCLOSURES: All Authors: No reported disclosures Oxford University Press 2023-11-27 /pmc/articles/PMC10678898/ http://dx.doi.org/10.1093/ofid/ofad500.1952 Text en © The Author(s) 2023. Published by Oxford University Press on behalf of Infectious Diseases Society of America. https://creativecommons.org/licenses/by/4.0/This is an Open Access article distributed under the terms of the Creative Commons Attribution License (https://creativecommons.org/licenses/by/4.0/), which permits unrestricted reuse, distribution, and reproduction in any medium, provided the original work is properly cited. |
spellingShingle | Abstract Park, Se Yoon Yu, Jungyeon Song, Jin Su Lee, Shin Young Kim, Jin Hwa Jeong, Yeon Su Oh, Sun Mi Kim, Tae Hyong Bae, Sanghwan Lee, Eunjung 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title | 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title_full | 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title_fullStr | 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title_full_unstemmed | 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title_short | 2330. Ventilation Strategies Based on an Aerodynamic Analysis During a Large-Scale SARS-CoV-2 Outbreak in an Acute-Care Hospital |
title_sort | 2330. ventilation strategies based on an aerodynamic analysis during a large-scale sars-cov-2 outbreak in an acute-care hospital |
topic | Abstract |
url | https://www.ncbi.nlm.nih.gov/pmc/articles/PMC10678898/ http://dx.doi.org/10.1093/ofid/ofad500.1952 |
work_keys_str_mv | AT parkseyoon 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT yujungyeon 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT songjinsu 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT leeshinyoung 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT kimjinhwa 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT jeongyeonsu 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT ohsunmi 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT kimtaehyong 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT baesanghwan 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital AT leeeunjung 2330ventilationstrategiesbasedonanaerodynamicanalysisduringalargescalesarscov2outbreakinanacutecarehospital |