Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system

The Sustainable Energy Development Authority of Malaysia (SEDA) regularly receives complaints about damaged components and distribution boards of PV systems due to lightning strikes. Permanent and momentary interruptions of distribution circuits may also occur from the disturbance. In this paper, a...

Descripción completa

Detalles Bibliográficos
Autores principales: Nasir, M. S. M., Ab-Kadir, M. Z. A., Radzi, M. A. M., Izadi, M., Ahmad, N. I., Zaini, N. H.
Formato: Online Artículo Texto
Lenguaje:English
Publicado: Public Library of Science 2019
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC6622495/
https://www.ncbi.nlm.nih.gov/pubmed/31295278
http://dx.doi.org/10.1371/journal.pone.0219326
_version_ 1783434166645293056
author Nasir, M. S. M.
Ab-Kadir, M. Z. A.
Radzi, M. A. M.
Izadi, M.
Ahmad, N. I.
Zaini, N. H.
author_facet Nasir, M. S. M.
Ab-Kadir, M. Z. A.
Radzi, M. A. M.
Izadi, M.
Ahmad, N. I.
Zaini, N. H.
author_sort Nasir, M. S. M.
collection PubMed
description The Sustainable Energy Development Authority of Malaysia (SEDA) regularly receives complaints about damaged components and distribution boards of PV systems due to lightning strikes. Permanent and momentary interruptions of distribution circuits may also occur from the disturbance. In this paper, a solar PV Rooftop system (3.91 kWp) provided by SEDA was modelled in the PSCAD/EMTDC. The Heidler function was used as a lightning current waveform model to analyse the transient current and voltage at two different points susceptible to the influence of lightning events such as different lightning current wave shape, standard lightning current and non-standard lightning current. This study examines the effect on the system components when lightning directly strikes at two different points of the installation. The two points lie between the inverter and the solar PV array and between inverter and grid. Exceptionally high current and voltage due to the direct lightning strike on a certain point of a PV Rooftop system was also studied. The result of this case study is observed with and without the inclusion of surge protective devices (SPDs). The parameters used were 31 kA of peak current, 10 metres cable length and lightning impulse current wave shape of 8/20μs. The high current and voltage at P1 striking point were 31 kA and 2397 kV, respectively. As for the AC part, the current and voltage values were found to be 5.97 kA and 5392 kV, respectively.Therefore, SPDs with suitable rating provided by SEDA were deployed. Results showed that high transient current voltage is expected to clamp sharply at the values of 1.915 kV and 0 A at the P1 striking point. As for the AC part, the current and voltage values were found to be 0 kA and 0.751 V, respectively. Varying lightning impulse current wave shapes at striking point P2 showed that the highest voltage was obtained at waveshape 10/350 μs at 11277 kV followed by wave shapes of 2/70 μs, 8/20 μs and 0.7/6 μs. The high value of transient voltage was clamped at a lower level of 2.029 kV. Different lightning amplitudes were also applied, ranging from 2–200 kA selected based on the CIGRE distribution. It showed that the current and voltage at P1 and P2 were directly proportional. Therefore, the SPD will be designed at an acceptable rating and proper position of SPD installation at solar PV Rooftop will be proposed. The results obtained in this study can then be utilised to appropriately assign a SPD to protect the PV systems that are connected to the grid. Installing SPDs without considering the needs of lightning protection zones would expose the expensive equipment to potential damage even though the proper energy coordination of SPDs is in place. As such, the simulation results provide a basis for controlling the impacts of direct lightning strikes on electrical equipment and power grids and thus justify SPD coordination to ensure the reliability of the system.
format Online
Article
Text
id pubmed-6622495
institution National Center for Biotechnology Information
language English
publishDate 2019
publisher Public Library of Science
record_format MEDLINE/PubMed
spelling pubmed-66224952019-07-25 Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system Nasir, M. S. M. Ab-Kadir, M. Z. A. Radzi, M. A. M. Izadi, M. Ahmad, N. I. Zaini, N. H. PLoS One Research Article The Sustainable Energy Development Authority of Malaysia (SEDA) regularly receives complaints about damaged components and distribution boards of PV systems due to lightning strikes. Permanent and momentary interruptions of distribution circuits may also occur from the disturbance. In this paper, a solar PV Rooftop system (3.91 kWp) provided by SEDA was modelled in the PSCAD/EMTDC. The Heidler function was used as a lightning current waveform model to analyse the transient current and voltage at two different points susceptible to the influence of lightning events such as different lightning current wave shape, standard lightning current and non-standard lightning current. This study examines the effect on the system components when lightning directly strikes at two different points of the installation. The two points lie between the inverter and the solar PV array and between inverter and grid. Exceptionally high current and voltage due to the direct lightning strike on a certain point of a PV Rooftop system was also studied. The result of this case study is observed with and without the inclusion of surge protective devices (SPDs). The parameters used were 31 kA of peak current, 10 metres cable length and lightning impulse current wave shape of 8/20μs. The high current and voltage at P1 striking point were 31 kA and 2397 kV, respectively. As for the AC part, the current and voltage values were found to be 5.97 kA and 5392 kV, respectively.Therefore, SPDs with suitable rating provided by SEDA were deployed. Results showed that high transient current voltage is expected to clamp sharply at the values of 1.915 kV and 0 A at the P1 striking point. As for the AC part, the current and voltage values were found to be 0 kA and 0.751 V, respectively. Varying lightning impulse current wave shapes at striking point P2 showed that the highest voltage was obtained at waveshape 10/350 μs at 11277 kV followed by wave shapes of 2/70 μs, 8/20 μs and 0.7/6 μs. The high value of transient voltage was clamped at a lower level of 2.029 kV. Different lightning amplitudes were also applied, ranging from 2–200 kA selected based on the CIGRE distribution. It showed that the current and voltage at P1 and P2 were directly proportional. Therefore, the SPD will be designed at an acceptable rating and proper position of SPD installation at solar PV Rooftop will be proposed. The results obtained in this study can then be utilised to appropriately assign a SPD to protect the PV systems that are connected to the grid. Installing SPDs without considering the needs of lightning protection zones would expose the expensive equipment to potential damage even though the proper energy coordination of SPDs is in place. As such, the simulation results provide a basis for controlling the impacts of direct lightning strikes on electrical equipment and power grids and thus justify SPD coordination to ensure the reliability of the system. Public Library of Science 2019-07-11 /pmc/articles/PMC6622495/ /pubmed/31295278 http://dx.doi.org/10.1371/journal.pone.0219326 Text en © 2019 Nasir et al http://creativecommons.org/licenses/by/4.0/ This is an open access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0/) , which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.
spellingShingle Research Article
Nasir, M. S. M.
Ab-Kadir, M. Z. A.
Radzi, M. A. M.
Izadi, M.
Ahmad, N. I.
Zaini, N. H.
Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title_full Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title_fullStr Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title_full_unstemmed Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title_short Lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
title_sort lightning performance analysis of a rooftop grid-connected solar photovoltaic without external lightning protection system
topic Research Article
url https://www.ncbi.nlm.nih.gov/pmc/articles/PMC6622495/
https://www.ncbi.nlm.nih.gov/pubmed/31295278
http://dx.doi.org/10.1371/journal.pone.0219326
work_keys_str_mv AT nasirmsm lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem
AT abkadirmza lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem
AT radzimam lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem
AT izadim lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem
AT ahmadni lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem
AT zaininh lightningperformanceanalysisofarooftopgridconnectedsolarphotovoltaicwithoutexternallightningprotectionsystem