Cargando…

An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete

Hot-dip Galvanized rebar (hereafter, HDG rebar) has an anti-corrosion effect due to the sacrificial anodic reaction of zinc. Additionally, the zinc coating itself provides barrier protection for the steel substrate. Meanwhile, from one of the investigations on the field performance of HDG rebar in c...

Descripción completa

Detalles Bibliográficos
Autores principales: Choe, Hong-bok, Nishio, Yuhei, Kanematsu, Manabu
Formato: Online Artículo Texto
Lenguaje:English
Publicado: MDPI 2019
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC6862703/
https://www.ncbi.nlm.nih.gov/pubmed/31671671
http://dx.doi.org/10.3390/ma12213566
_version_ 1783471615737069568
author Choe, Hong-bok
Nishio, Yuhei
Kanematsu, Manabu
author_facet Choe, Hong-bok
Nishio, Yuhei
Kanematsu, Manabu
author_sort Choe, Hong-bok
collection PubMed
description Hot-dip Galvanized rebar (hereafter, HDG rebar) has an anti-corrosion effect due to the sacrificial anodic reaction of zinc. Additionally, the zinc coating itself provides barrier protection for the steel substrate. Meanwhile, from one of the investigations on the field performance of HDG rebar in concrete, HDG rebar did not protect the substrate when the remaining zinc was under 50 µm. For the evaluation of this property over a short period of time, an acceleration test using impressed anodic current (hereafter, acceleration test) may be useful. This test impresses constant direct current into the rebar and can result in the intended quantitative extent of the anodic reaction. However, in using this test on HDG rebar, it was found that the high rate of applied current density could cause an unintended early end of the anti-corrosion effect of zinc, despite there being more than 50 µm of remaining zinc thickness. In this study, the usability of the acceleration test was investigated to determine if it is a suitable method for evaluating the anti-corrosion behavior of HDG rebar in concrete. As a test variable, a comparatively low rate of applied current density was used in the experiments. As a result, it was clarified that an effective corrosion protection of the substrate was made with an increase of the zinc corrosion amount. This anti-corrosion effect was similar to that known to exist in actual corrosion environments. This behavior was terminated when the concrete cracked, and the substrate became corroded. While the test condition in this study resulted in an early end of the anti-corrosion effect of zinc, a linear correlation was achieved between the applied current density and the remaining zinc thickness at the time that the anti-corrosion effect was terminated. It was found that lowering the applied current density resulted in a more suitable test condition. In conclusion, the acceleration test was found to be useful, although further experimental validation is necessary to confirm this finding.
format Online
Article
Text
id pubmed-6862703
institution National Center for Biotechnology Information
language English
publishDate 2019
publisher MDPI
record_format MEDLINE/PubMed
spelling pubmed-68627032019-12-05 An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete Choe, Hong-bok Nishio, Yuhei Kanematsu, Manabu Materials (Basel) Article Hot-dip Galvanized rebar (hereafter, HDG rebar) has an anti-corrosion effect due to the sacrificial anodic reaction of zinc. Additionally, the zinc coating itself provides barrier protection for the steel substrate. Meanwhile, from one of the investigations on the field performance of HDG rebar in concrete, HDG rebar did not protect the substrate when the remaining zinc was under 50 µm. For the evaluation of this property over a short period of time, an acceleration test using impressed anodic current (hereafter, acceleration test) may be useful. This test impresses constant direct current into the rebar and can result in the intended quantitative extent of the anodic reaction. However, in using this test on HDG rebar, it was found that the high rate of applied current density could cause an unintended early end of the anti-corrosion effect of zinc, despite there being more than 50 µm of remaining zinc thickness. In this study, the usability of the acceleration test was investigated to determine if it is a suitable method for evaluating the anti-corrosion behavior of HDG rebar in concrete. As a test variable, a comparatively low rate of applied current density was used in the experiments. As a result, it was clarified that an effective corrosion protection of the substrate was made with an increase of the zinc corrosion amount. This anti-corrosion effect was similar to that known to exist in actual corrosion environments. This behavior was terminated when the concrete cracked, and the substrate became corroded. While the test condition in this study resulted in an early end of the anti-corrosion effect of zinc, a linear correlation was achieved between the applied current density and the remaining zinc thickness at the time that the anti-corrosion effect was terminated. It was found that lowering the applied current density resulted in a more suitable test condition. In conclusion, the acceleration test was found to be useful, although further experimental validation is necessary to confirm this finding. MDPI 2019-10-30 /pmc/articles/PMC6862703/ /pubmed/31671671 http://dx.doi.org/10.3390/ma12213566 Text en © 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
spellingShingle Article
Choe, Hong-bok
Nishio, Yuhei
Kanematsu, Manabu
An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title_full An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title_fullStr An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title_full_unstemmed An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title_short An Investigation on the Usability of Acceleration Test by Impressed Anodic Current for Evaluating Corrosion Behavior of Hot-Dip Galvanized Rebar in Concrete
title_sort investigation on the usability of acceleration test by impressed anodic current for evaluating corrosion behavior of hot-dip galvanized rebar in concrete
topic Article
url https://www.ncbi.nlm.nih.gov/pmc/articles/PMC6862703/
https://www.ncbi.nlm.nih.gov/pubmed/31671671
http://dx.doi.org/10.3390/ma12213566
work_keys_str_mv AT choehongbok aninvestigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete
AT nishioyuhei aninvestigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete
AT kanematsumanabu aninvestigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete
AT choehongbok investigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete
AT nishioyuhei investigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete
AT kanematsumanabu investigationontheusabilityofaccelerationtestbyimpressedanodiccurrentforevaluatingcorrosionbehaviorofhotdipgalvanizedrebarinconcrete