Cargando…

Air infiltration induced inter-unit dispersion and infectious risk assessment in a high-rise residential building

Identifying possible airborne transmission routes and assessing the associated infectious risks are essential for implementing effective control measures. This study focuses on the infiltration-induced inter-unit pollutant dispersion in a high-rise residential (HRR) building. The outdoor wind pressu...

Descripción completa

Detalles Bibliográficos
Autores principales: Wu, Yan, Niu, Jianlei, Liu, Xiaoping
Formato: Online Artículo Texto
Lenguaje:English
Publicado: Tsinghua University Press 2017
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC7090850/
https://www.ncbi.nlm.nih.gov/pubmed/32218902
http://dx.doi.org/10.1007/s12273-017-0388-6
Descripción
Sumario:Identifying possible airborne transmission routes and assessing the associated infectious risks are essential for implementing effective control measures. This study focuses on the infiltration-induced inter-unit pollutant dispersion in a high-rise residential (HRR) building. The outdoor wind pressure distribution on the building facades was obtained from the wind tunnel experiments. And the inter-household infiltration and tracer gas transmission were simulated using multi-zone model. The risk levels along building height and under different wind directions were examined, and influence of component leakage area was analysed. It is found that, the cross-infection risk can be over 20% because of the low air infiltration rate below 0.7 ACH, which is significantly higher than the risk of 9% obtained in our previous on-site measurement with air change rate over 3 ACH. As the air infiltration rate increases along building height, cross-infection risk is generally higher on the lower floors. The effect of wind direction on inter-unit dispersion level is significant, and the presence of a contaminant source in the windward side results in the highest cross-infection risks in other adjacent units on the same floor. Properly improving internal components tightness and increasing air change via external components are beneficial to the control of internal inter-unit transmission induced by infiltration. However, this approach may increase the cross-infection via the external transmission, and effective control measures should be further explored considering multiple transmission routes.