Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review

Air cleaning techniques have been applied worldwide with the goal of improving indoor air quality. The effectiveness of applying these techniques varies widely, and pollutant removal efficiency is usually determined in controlled laboratory environments which may not be realized in practice. Some ai...

Descripción completa

Detalles Bibliográficos
Autores principales: Zhang, Yinping, Mo, Jinhan, Li, Yuguo, Sundell, Jan, Wargocki, Pawel, Zhang, Jensen, Little, John C., Corsi, Richard, Deng, Qihong, Leung, Michael H.K., Fang, Lei, Chen, Wenhao, Li, Jinguang, Sun, Yuexia
Formato: Online Artículo Texto
Lenguaje:English
Publicado: Elsevier Ltd. 2011
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC7185562/
https://www.ncbi.nlm.nih.gov/pubmed/32362761
http://dx.doi.org/10.1016/j.atmosenv.2011.05.041
_version_ 1783526782284070912
author Zhang, Yinping
Mo, Jinhan
Li, Yuguo
Sundell, Jan
Wargocki, Pawel
Zhang, Jensen
Little, John C.
Corsi, Richard
Deng, Qihong
Leung, Michael H.K.
Fang, Lei
Chen, Wenhao
Li, Jinguang
Sun, Yuexia
author_facet Zhang, Yinping
Mo, Jinhan
Li, Yuguo
Sundell, Jan
Wargocki, Pawel
Zhang, Jensen
Little, John C.
Corsi, Richard
Deng, Qihong
Leung, Michael H.K.
Fang, Lei
Chen, Wenhao
Li, Jinguang
Sun, Yuexia
author_sort Zhang, Yinping
collection PubMed
description Air cleaning techniques have been applied worldwide with the goal of improving indoor air quality. The effectiveness of applying these techniques varies widely, and pollutant removal efficiency is usually determined in controlled laboratory environments which may not be realized in practice. Some air cleaners are largely ineffective, and some produce harmful by-products. To summarize what is known regarding the effectiveness of fan-driven air cleaning technologies, a state-of-the-art review of the scientific literature was undertaken by a multidisciplinary panel of experts from Europe, North America, and Asia with expertise in air cleaning, aerosol science, medicine, chemistry and ventilation. The effects on health were not examined. Over 26,000 articles were identified in major literature databases; 400 were selected as being relevant based on their titles and abstracts by the first two authors, who further reduced the number of articles to 160 based on the full texts. These articles were reviewed by the panel using predefined inclusion criteria during their first meeting. Additions were also made by the panel. Of these, 133 articles were finally selected for detailed review. Each article was assessed independently by two members of the panel and then judged by the entire panel during a consensus meeting. During this process 59 articles were deemed conclusive and their results were used for final reporting at their second meeting. The conclusions are that: (1) None of the reviewed technologies was able to effectively remove all indoor pollutants and many were found to generate undesirable by-products during operation. (2) Particle filtration and sorption of gaseous pollutants were among the most effective air cleaning technologies, but there is insufficient information regarding long-term performance and proper maintenance. (3) The existing data make it difficult to extract information such as Clean Air Delivery Rate (CADR), which represents a common benchmark for comparing the performance of different air cleaning technologies. (4) To compare and select suitable indoor air cleaning devices, a labeling system accounting for characteristics such as CADR, energy consumption, volume, harmful by-products, and life span is necessary. For that purpose, a standard test room and condition should be built and studied. (5) Although there is evidence that some air cleaning technologies improve indoor air quality, further research is needed before any of them can be confidently recommended for use in indoor environments.
format Online
Article
Text
id pubmed-7185562
institution National Center for Biotechnology Information
language English
publishDate 2011
publisher Elsevier Ltd.
record_format MEDLINE/PubMed
spelling pubmed-71855622020-04-28 Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review Zhang, Yinping Mo, Jinhan Li, Yuguo Sundell, Jan Wargocki, Pawel Zhang, Jensen Little, John C. Corsi, Richard Deng, Qihong Leung, Michael H.K. Fang, Lei Chen, Wenhao Li, Jinguang Sun, Yuexia Atmos Environ (1994) Article Air cleaning techniques have been applied worldwide with the goal of improving indoor air quality. The effectiveness of applying these techniques varies widely, and pollutant removal efficiency is usually determined in controlled laboratory environments which may not be realized in practice. Some air cleaners are largely ineffective, and some produce harmful by-products. To summarize what is known regarding the effectiveness of fan-driven air cleaning technologies, a state-of-the-art review of the scientific literature was undertaken by a multidisciplinary panel of experts from Europe, North America, and Asia with expertise in air cleaning, aerosol science, medicine, chemistry and ventilation. The effects on health were not examined. Over 26,000 articles were identified in major literature databases; 400 were selected as being relevant based on their titles and abstracts by the first two authors, who further reduced the number of articles to 160 based on the full texts. These articles were reviewed by the panel using predefined inclusion criteria during their first meeting. Additions were also made by the panel. Of these, 133 articles were finally selected for detailed review. Each article was assessed independently by two members of the panel and then judged by the entire panel during a consensus meeting. During this process 59 articles were deemed conclusive and their results were used for final reporting at their second meeting. The conclusions are that: (1) None of the reviewed technologies was able to effectively remove all indoor pollutants and many were found to generate undesirable by-products during operation. (2) Particle filtration and sorption of gaseous pollutants were among the most effective air cleaning technologies, but there is insufficient information regarding long-term performance and proper maintenance. (3) The existing data make it difficult to extract information such as Clean Air Delivery Rate (CADR), which represents a common benchmark for comparing the performance of different air cleaning technologies. (4) To compare and select suitable indoor air cleaning devices, a labeling system accounting for characteristics such as CADR, energy consumption, volume, harmful by-products, and life span is necessary. For that purpose, a standard test room and condition should be built and studied. (5) Although there is evidence that some air cleaning technologies improve indoor air quality, further research is needed before any of them can be confidently recommended for use in indoor environments. Elsevier Ltd. 2011-08 2011-05-25 /pmc/articles/PMC7185562/ /pubmed/32362761 http://dx.doi.org/10.1016/j.atmosenv.2011.05.041 Text en Copyright © 2011 Elsevier Ltd. All rights reserved. Since January 2020 Elsevier has created a COVID-19 resource centre with free information in English and Mandarin on the novel coronavirus COVID-19. The COVID-19 resource centre is hosted on Elsevier Connect, the company's public news and information website. Elsevier hereby grants permission to make all its COVID-19-related research that is available on the COVID-19 resource centre - including this research content - immediately available in PubMed Central and other publicly funded repositories, such as the WHO COVID database with rights for unrestricted research re-use and analyses in any form or by any means with acknowledgement of the original source. These permissions are granted for free by Elsevier for as long as the COVID-19 resource centre remains active.
spellingShingle Article
Zhang, Yinping
Mo, Jinhan
Li, Yuguo
Sundell, Jan
Wargocki, Pawel
Zhang, Jensen
Little, John C.
Corsi, Richard
Deng, Qihong
Leung, Michael H.K.
Fang, Lei
Chen, Wenhao
Li, Jinguang
Sun, Yuexia
Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title_full Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title_fullStr Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title_full_unstemmed Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title_short Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review
title_sort can commonly-used fan-driven air cleaning technologies improve indoor air quality? a literature review
topic Article
url https://www.ncbi.nlm.nih.gov/pmc/articles/PMC7185562/
https://www.ncbi.nlm.nih.gov/pubmed/32362761
http://dx.doi.org/10.1016/j.atmosenv.2011.05.041
work_keys_str_mv AT zhangyinping cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT mojinhan cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT liyuguo cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT sundelljan cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT wargockipawel cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT zhangjensen cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT littlejohnc cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT corsirichard cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT dengqihong cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT leungmichaelhk cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT fanglei cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT chenwenhao cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT lijinguang cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview
AT sunyuexia cancommonlyusedfandrivenaircleaningtechnologiesimproveindoorairqualityaliteraturereview