Cargando…

Cooling System with PCM Storage for an Office Building: Experimental Investigation Aided by a Model of the Office Thermal Dynamics

The application of energy storage filled with phase-change material (PCM) is recently increasingly considered in active cooling systems. Such a design offers a higher density of thermal energy accumulation when compared with water storage. However, the optimum use of PCM storage is possible when its...

Descripción completa

Detalles Bibliográficos
Autor principal: Karwacki, Jarosław
Formato: Online Artículo Texto
Lenguaje:English
Publicado: MDPI 2021
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC7998234/
https://www.ncbi.nlm.nih.gov/pubmed/33799671
http://dx.doi.org/10.3390/ma14061356
Descripción
Sumario:The application of energy storage filled with phase-change material (PCM) is recently increasingly considered in active cooling systems. Such a design offers a higher density of thermal energy accumulation when compared with water storage. However, the optimum use of PCM storage is possible when its dynamic characteristics during the loading and unloading process are well recognized. Due to the complexity of the interaction between all elements of the heating/cooling system, a theoretical estimation of the profits is hard to perform in a reliable way. This is a significant problem at the design stage of the installation. In order to solve this problem, a laboratory experiment supported by a simulation was performed. The main aim of the experiment was to understand how the storage filled with the PCM in real-like conditions works. A test stand was made to investigate the effect of this solution on a reduced scale of 1:10. The PCM tested was RT15, a commercially available material that melts in the temperature range of 10–17 °C. The main parts of the stand are a chiller, an electric heater and thermal energy storage. The first two elements allowed a simulation of the thermal properties of the heat receiver, and their operation depended on the results from the numerical calculations. A lumped parameter model was used in mathematical description of the office building and its cooling system. The heat capacity of the system components as well as heat losses to the ambient environment were taken into account. The obtained results allowed the optimization of the control procedure and proved the validity of the applied investigation methods. This study confirmed the possibility of testing thermal energy storage with phase change material in real-like conditions.