Cargando…

Diagnosis of Partial Discharge Based on the Air Components for the 10 kV Air-Insulated Switchgear

Partial discharge (PD) is a common phenomenon of insulation aging in air-insulated switchgear and will change the gas composition in the equipment. However, it is still a challenge to diagnose and identify the defect types of PD. This paper conducts enclosed experiments based on gas sensors to obtai...

Descripción completa

Detalles Bibliográficos
Autores principales: Tan, Qipeng, Zhang, Tiandong, Wu, Shaocheng, Gao, Jiachen, Song, Bin
Formato: Online Artículo Texto
Lenguaje:English
Publicado: MDPI 2022
Materias:
Acceso en línea:https://www.ncbi.nlm.nih.gov/pmc/articles/PMC8948649/
https://www.ncbi.nlm.nih.gov/pubmed/35336566
http://dx.doi.org/10.3390/s22062395
Descripción
Sumario:Partial discharge (PD) is a common phenomenon of insulation aging in air-insulated switchgear and will change the gas composition in the equipment. However, it is still a challenge to diagnose and identify the defect types of PD. This paper conducts enclosed experiments based on gas sensors to obtain the concentration data of the characteristic gases CO, NO(2), and O(3) under four typical defects. The random forest algorithm with grid search optimization is used for fault identification to explore a method of identifying defect types through gas concentration. The results show that the gases concentration variations do have statistical characteristics, and the RF algorithm can achieve high accuracy in prediction. The combination of a sensor and a machine learning algorithm provides the gas component analysis method a way to diagnose PD in an air-insulated switchgear.