Cargando…
New Smart Sensor for Voltage Unbalance Measurements in Electrical Power Systems
This paper deals with voltage unbalances and how they can be quantified according to the standards. Firstly, a comparison between the different unbalance voltage factors is conducted in order to remark on their divergences. Secondly, according to the standard that better represents the phenomenon, i...
Autores principales: | , , |
---|---|
Formato: | Online Artículo Texto |
Lenguaje: | English |
Publicado: |
MDPI
2022
|
Materias: | |
Acceso en línea: | https://www.ncbi.nlm.nih.gov/pmc/articles/PMC9659007/ https://www.ncbi.nlm.nih.gov/pubmed/36365933 http://dx.doi.org/10.3390/s22218236 |
Sumario: | This paper deals with voltage unbalances and how they can be quantified according to the standards. Firstly, a comparison between the different unbalance voltage factors is conducted in order to remark on their divergences. Secondly, according to the standard that better represents the phenomenon, i.e., EN 50160, a new methodology is proposed to quantify the voltage unbalance factor (VUF). In order to do so, it is recommended to measure the voltage unbalance in three-phase installations by means of a new smart sensor based on a single voltage sensor, which measures the direct-current (DC) voltage at the output of a three-phase diode bridge rectifier, while current methods make use of three voltage sensors (which can measure either phase-to-neutral voltages or phase-to-phase voltages). Furthermore, both simulation and experimental results have been carried out to validate the proposed methodology. Finally, a new voltage unbalance factor (and the corresponding methodology to obtain it from the measured DC voltage) is proposed. |
---|